{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Information for Noise level of UPS Galaxy PW

Issue:
Information for Noise level of UPS Galaxy PW.


Product line:
Galaxy PW US


Environment:
Galaxy PW 150KVA US
Galaxy PW 225KVA US


Cause:
Customer needs UPS room noise level with Galaxy PW.


Resolution:
We publish this information. for Galaxy PW UPS.

Noise levels
Noise levels are measured according to standard ISO 3746 (NFS 31 027).
UPS noise levels are indicated below:

UPS rating in KVA100130150180200225
Noise level on normal floor (dBA)626364656768

The noise level is identical for linear and non-linear loads.






Schneider Electric Vietnam

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: