You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Issue:
How to setup basic S-Flex PID control?
Product Line:
Altivar Machines, S-Flex
Environment:
Series E units with BYP feature
Cause:
Requires PID control in AUTO, but no PID control in HAND
Resolution:
Search other FAQs for details on ATV212 PID settings. This FAQ addresses the control concept. The settings listed are changes from the S-Flex factory defaults.
Option 1 = PID control in both HAND and AUTO
F360 = 1(VIA) or 2(VIB) for the analog feedback signal
FMOd = 3 for HMI setpoint adjustment when in AUTO
F207 = 3 for HMI setpoint adjustment when in HAND
Option 2 = PID control in AUTO, HMI speed reference in HAND
F360 = 1(VIA) for the analog feedback signal
Add a potentiometer to PP-VIB-CC
FMOd = 2(VIB) for PID setpoint adjustment when in AUTO
Remove the wire from DOC-14 to VFD terminal R and add a jumper wire between VFD terminals R - RES
F110 = 1 for always active run permissive
F112 = 14 for PID deactivate when in HAND
The potentiometer modification for Option 2 is required because an HMI PID setpoint and an HMI HAND speed reference will conflict with each other. Changing one changes the other.
How to setup basic S-Flex PID control?
Product Line:
Altivar Machines, S-Flex
Environment:
Series E units with BYP feature
Cause:
Requires PID control in AUTO, but no PID control in HAND
Resolution:
Search other FAQs for details on ATV212 PID settings. This FAQ addresses the control concept. The settings listed are changes from the S-Flex factory defaults.
Option 1 = PID control in both HAND and AUTO
F360 = 1(VIA) or 2(VIB) for the analog feedback signal
FMOd = 3 for HMI setpoint adjustment when in AUTO
F207 = 3 for HMI setpoint adjustment when in HAND
Option 2 = PID control in AUTO, HMI speed reference in HAND
F360 = 1(VIA) for the analog feedback signal
Add a potentiometer to PP-VIB-CC
FMOd = 2(VIB) for PID setpoint adjustment when in AUTO
Remove the wire from DOC-14 to VFD terminal R and add a jumper wire between VFD terminals R - RES
F110 = 1 for always active run permissive
F112 = 14 for PID deactivate when in HAND
The potentiometer modification for Option 2 is required because an HMI PID setpoint and an HMI HAND speed reference will conflict with each other. Changing one changes the other.