Issue:
ATV212 setup for forced local
Product Line:
Altivar 212
Environment:
All
Cause:
Might be using communications for monitoring but controlling by the drive's terminals
Resolution:
Forced local can be triggered by either of two ways:
ATV212 setup for forced local
Product Line:
Altivar 212
Environment:
All
Cause:
Might be using communications for monitoring but controlling by the drive's terminals
Resolution:
Forced local can be triggered by either of two ways:
- Assigning F108 (always active logic) to 48, which keeps forced local active
- Assigning F113 (RES terminal) to 48, which triggers forced local when RES is active