{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

Characteristics of the inverse time-delay over-current opening releases at the reference temperature of Acti 9 iC60 circuit breakers based on IEC 60898-1 and IEC 60947-2 specifications

The derating table (attached) for the iC60 devices are based on testing with respect to IEC 60898-1 and IEC 60947-2 requirements.

Standard IEC 60898-1:
  • Testing is to be done at temperature reference 30°C
  • Conventional non-tripping current 1.13 x In
  • Conventional tripping current 1.45 x In
  • Conventional time 1h

Standard IEC 60947-2:
  • Conventional non-tripping current 1.05 x In
  • Conventional tripping current 1.3 x In
  • Conventional time 1h
  • Each manufacturer defines the ambient reference temperature.
50°C for MCB compliant with both standards (IEC 60898-1 and IEC 60947-2)
40°C for MCB compliant only with IEC 60947-2

Furthermore, the manufacturer is responsible to include the reference temperature of the test at rated current, printed on the device as follows:

For more information concerning the 2 standards, please visit the blog:

https://blog.schneider-electric.com/energy-regulations/2014/02/06/iec-60898-1-iec-60947-2-tale-two-standards/

Schneider Electric Vietnam

Attachment(s)

Acti9_AmbientTemp.pdfActi9_AmbientTemp.pdf [264.12 KB]
Explore more
Range:
Acti9 iC60
Explore more
Range:
Acti9 iC60
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.