Search FAQs
You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
What is the operating time of ground fault protection devices defined in the UL 1053 standard?
The UL 1053 standard defines in Table 22.1 the operating time of the ground fault protection devices:
Ground-fault current (A) | Time (s) |
85% of pickup current | Shall not trip |
115% of pickup current | Ultimately |
150% of pickup current | 2 |
250% of pickup current | 1 |
Released for:Schneider Electric Vietnam
Explore more
Range:
Explore more
Range: