How is the ATV212 set for RUN/STOP on the terminals and speed reference from the keypad UP/DOWN arrows?

Article available in these languages: Spanish

Issue:
Trying to set the ATV212  for RUN/STOP on the terminals and UP/DOWN arrows for the speed reference.

Product Line:
Altivar Machines, Altivar 212

Environment:
All models and serial numbers

Cause:
Customer needs to use terminals for Start/Stop and Arrows on the faceplate of drive for speed reference

Resolution:
Set CNOD = 0 for terminals Start/Stop control.
Set FNOD = 3 for keypad UP/DOWN arrow button speed control.