{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

Steps to restore SmartX Advanced Display applications, a part of the EcoStruxure™ Building Operation

1. Obtain Serial number & Firmware version form SmartX AD panel for compatibility consideration and documentation purpose
2. Clean SmartX AD panel, uninstall unsupported or corrupted applications
3.  Install applications: SmartX AD-Link, SmartKiosk, alternatively Technician Tool for version 1.x.x of SmartX controllers.  Smart X AD SM-T580 must be T580XXU4CSA1 or above.
(For Android 8.1: SmartX AD-Link v8.0.apk, SmartXKiosk v8.1.apk, SBO Technician Tool_v1.4.0.91.apk)
4. Delete installation source files from SmartX AD panel file system
5. Activate applications according Smart X ID installation guide

Schneider Electric Vietnam

Attachment(s)

TPA-EBO-19-0002.00 SmartX Advanced Display Android 8 Compatibility.pdfTPA-EBO-19-0002.00 SmartX Advanced Display Android 8 Compatibility.pdf [120.54 KB]
AD v2 - SmartStruxure Solution - Installation Sheet.pdfAD v2 - SmartStruxure Solution - Installation Sheet.pdf [595.12 KB]
AD step by step guide.pdfAD step by step guide.pdf [261.2 KB]
Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.