{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

Does LC1D80BD have internal bi-directional diode?

Issue:
LC1D80 and LC1D95 bi-directional diode

Product Line:
TeSys™ D Contactors

Environment:
Contactor Accessories

Resolution:
LC1D80 and LC1D95 does not have an internal bi-directional peak limiting diode on their DC coils. LA4DC3U (Screw connection of wire to the contactor coil terminals 24–250 Vdc, 3p-4p) must be ordered separately.

The LC1D09 to LC1D38 have an internal diode by default on their DC coils.

Schneider Electric Vietnam

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: