How to perform a factory reset on the ATV320 drive?
Issue:
Factory reset on the ATV320 drive.

Product Line:
Altivar 320

Environment:
All

Cause:
Factory reset.

Resolution:
To perform a factory reset from power up;
Enter on dial.
Scroll to CONF menu and enter.
Scroll to FCS- and enter.
Scroll to FRY- and enter.
Select All so that " mark is at top instead of bottom.
Now go to GFS parameter.
Set it to YES and hold enter for 2 seconds until display LEDs stop flashing.
VFD is rest to factory defaults.