As for the BMXNOR0200 platform, what’s the equivalent function of clear events in IEC101/IEC104? BMXNOR0200, IEC101/IEC104
We have the equivalent command in the IEC101/IEC104 protocol.
It is C_RP with QRP=2: reset of pending information with time tag of the event bugger.
[NOR has no interface]
We have the equivalent command in the IEC101/IEC104 protocol.
It is C_RP with QRP=2: reset of pending information with time tag of the event bugger.
[NOR has no interface]