{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Should the long time rating plug be removed before insulation and dielectric withstand test in MVS Micrologic?
It is not necessary to remove long time rating plug in Micrologic ET2/ETA2/ ET5S/ETA5S/ ET6G/ETA6G before before insulation and dielectric withstand test .
It is absolutely necessary to remove long time rating plug in Micrologic ETV2I/ ETV5S/ ETV6G before insulation and dielectric withstand test

Schneider Electric Vietnam

Explore more
Product:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product: