How are the units setup when reading Modbus address 3204 Motor current?

Issue:

Customer is not getting back what he expects when reading motor current 3204 over Modbus.

Product Line:

Altivar drives

Environment:

All

Cause:

Reading Modbus register 3204

Resolution:

Register 3204, Motor current, reads in tenths. Example 200 = 20.0A.

Schneider Electric Vietnam