{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Why am I getting "An error happened; will automatically restart" on my HMISTW when trying to view Webvisu?

Issue:

Why am I getting "An error happened; will automatically restart" on my HMISTW when trying to view Webvisu?

Product Line:

HMISTW

Resolution:
This error usually occurs when the HMISTW is running an older firmware version.
Last official firmware: 1.1.0 (26 Oct, 2020)

Please see this FAQ on how to update the HMISTW firmware:
https://www.se.com/ww/en/faqs/FA403854/

HMISTW error with Webvisu

Here is how to check which firmware version your HMISTW is running:
1. Open the configuration menu on the HMISTW
2. Click "+ Information" to expand
3. There you will be able to check with version currently running.
version

Schneider Electric Vietnam

Explore more
Product:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product: