Context: Example BusCycle EIP configuration (IEC 61499) between BMED581020 and BMEP586040.
BusCycleTime must be greater than RPI O -> T + RPI T -> O
Example:
BusCycleTime (80ms) >> RPI O -> T (30ms) + RPI T -> O (30ms)
Note: if there are several devices, take the highest RPI O -> T and RPI T -> O.
Product line:
EAE, EIP, Buscycle, Time, BMED581020, IEC 61499
Environment:
Windows, EcoStruxure Automation Expert 22.0
BusCycleTime must be greater than RPI O -> T + RPI T -> O
Example:
BusCycleTime (80ms) >> RPI O -> T (30ms) + RPI T -> O (30ms)
Note: if there are several devices, take the highest RPI O -> T and RPI T -> O.
Product line:
EAE, EIP, Buscycle, Time, BMED581020, IEC 61499
Environment: