{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

How to configure EIP buscycle with BMED581020 (IEC 61499)

Context: Example BusCycle EIP configuration (IEC 61499) between BMED581020 and BMEP586040.
EIP configuration BMED581020

BMED581020 EIP configuration buscycle

BusCycleTime must be greater than RPI O -> T + RPI T -> O

Example:
BusCycleTime (80ms) >> RPI O -> T (30ms) + RPI T -> O (30ms)

Note: if there are several devices, take the highest RPI O -> T and RPI T -> O.


Product line:
EAE, EIP, Buscycle, Time, BMED581020, IEC 61499
Environment:
Windows, EcoStruxure Automation Expert 22.0

Schneider Electric Vietnam

Explore more
Product:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product: