{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
What are the units when reading LCR or motor current over Ethernet on the ATV340 Drive?

Issue:

LCR address 3204 motor current units or values for the ATV340 Drives.

Product Line:

ATV340 Drives.

Environment:

All

Cause:

Motor amps are reading to high over Ethernet or address 3204 LCr.

Resolution:

The unit of LCR are

From ATV340 0.75kw to ATV340 15kw, the unit is 0.01A.

From ATV340 18.5kw to ATV340 75kw, the unit is 0.1A .

Schneider Electric Vietnam

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: