Issue:
HMI VW3A1111 directly to the Ethernet network?
Product Line:
ATV600 and ATV900
Environment:
All
Cause:
Wants to connect the remote HMI to the Ethernet network.
Resolution:
No, the VW3A1111 remote HMI cannot be connected directly to the Ethernet network.
The remote HMI or Graphic Display Terminal is only compatible with the Modbus port built into the drive. The HMI modbus settings baud 19.2k format 8E1