Can I-line II busway be installed under a raised floor?
Issue:
Needs to install busway under a raised floor
Product Line:
Busway
Environment:
I-line II Busway
Cause:
N/A
Resolution:
Our I-Line II busway can be installed under "raised floors" as long as the busway joints and support system are accessible and the space is not used as return air systems.
Released for:Schneider Electric Vietnam