{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Monitoring ATV212 Analog Input signals on HMI

Issue:

Can I monitor Analog Input signals on ATV212 display?

Product Line:

ATV21, ATV212

Environment:

All

Cause:

Want to confirm analog input signal strength wired to VFD.

Resolution:

It is not possible to monitor the VIA or VIB signal values on the HMI display.

Schneider Electric Vietnam

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: