{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

ION9000 Data Not Showing on Connected Panel Server

Issue: ION9000 is serially connected to Panel Server. Registers can be read on the panel server and through Modscan but data is not populating on the panel server webpage.

Product Line:

ION9000
EcoStruxure  Panel Server - Advanced
EcoStruxure  Panel Server - Universal

Environment:

Panel Server Webpage

Cause: The Panel Server does not have a native device file for the ION9000.

Resolution:

A custom device file will have to be created in order to see data. This can be done in EcoStruxure Power Commission. Reference:

Custom Models for Downstream Modbus Devices (Universal and Advanced Models)

Schneider Electric Vietnam

Attachment(s)

Panel Server - User Guide - 2022.pdfPanel Server - User Guide - 2022.pdf [31.27 MB]
Explore more
Range:
EcoStruxure Panel ServerPowerLogic™ ION9000
Explore more
Range:
EcoStruxure Panel ServerPowerLogic™ ION9000
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.