{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

Control Power Transformers 3kVA and 5kVA should be installed on its own instrument compartment?

Issue:
Control power transformers: 3 and 5 kVA on its own instrument compartment.
Product Line:
Power Zone 4 Switchgear and QED6 Switchboard
Environment:
Power Products
Cause:
Can be installed additional components no associated to 3kVA or 5kVA transformers and primary and secondary protection in same instrument compartment?
Resolution:
Investigated with UL File - Vol SQ section General, Transformers rated 3000-5000VA shall be mounted in a compartment, otherwise empty, of minimum dimensions 21 by 21 by 15 in. so as long as we can meet that min. space for that application, a compartment may be shared with small components that don't protrude that space.

Schneider Electric Vietnam

Explore more
Range:
QED-6 Rear Connected SwitchboardsPower-Zone 4 Front AccessiblePower-Zone 4 Arc Resistant Low Voltage Switchgear with...Power-Zone 4 Low Voltage Switchgear with Masterpact NW and...
Explore more
Range:
QED-6 Rear Connected SwitchboardsPower-Zone 4 Front AccessiblePower-Zone 4 Arc Resistant Low Voltage Switchgear with...Power-Zone 4 Low Voltage Switchgear with Masterpact NW and...
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.