{}

Nhãn hiệu của chúng tôi

Impact-Company-Logo-English Black-01-177x54

Chào mừng bạn đến với Trang web của Schneider Electric

Chào mừng đến với trang web của chúng tôi.

Tìm các câu hỏi thường gặp

Does the ATV312 cooling fan run all the time?

Issue:
Is the cooling fan on ATV312 drive running all the time?

Product Line:
ATV312

Environment:
All model numbers, all serial numbers

Cause:
N/A

Resolution:
The fan starts automatically when the drive controller is commanded to run (receives a run command and a speed reference). It stops a few seconds
after the drive controller is stopped (when output frequency is less than 0.5 Hz and DC injection braking is completed). Not all units have a cooling fan.
NOTE: The fan may start without a run command if the drive controller temperature exceeds allowable limits.

Schneider Electric Việt Nam

Tìm hiểu thêm
Danh mục:
AC Drives and Soft Starters
Phạm vi:
Altivar 312Altivar 31C
Tìm hiểu thêm
Danh mục:
AC Drives and Soft Starters
Phạm vi:
Altivar 312Altivar 31C