{}

Nhãn hiệu của chúng tôi

Impact-Company-Logo-English Black-01-177x54

Chào mừng bạn đến với Trang web của Schneider Electric

Chào mừng đến với trang web của chúng tôi.

Tìm các câu hỏi thường gặp

How to Determine if Cumulative Update 3 has been applied to a StruxureWare Power Monitoring 7.0.1 System

Issue
There is no direct way of finding, If cumulative update 3 has been installed for a SPM 7.0.1 system.

Product Line
Struxtureware Power Monitoring 7.0.1

Environment
Windows 7
Windows Server 2008
Struxtureware Power Monitoring 7.0.1

Cause
No update available in the Help > About section

Resolution
There is no way to tell if Cumulative Update 3 has been applied to a StruxureWare Power Monitoring 7.0.1 System in by looking at the version/build number in Help> About, but it can be determined from the registry.

Cumulative Update 3 adds the registry setting IONSERVICESCACHEPOLLINGRATE and can be found under HKEY_LOCAL_MACHIN\SOFTWARE\Wow6432Node\Schneider Electric\ION Enterprise\7.0.1

If IONSERVICESCACHEPOLLINGRATE is found at the above location Cumulative Update 3 has been applied.

If IONSERVICESCACHEPOLLINGRATE is not found at that location Cumulative Update 3 has not been run.

Schneider Electric Việt Nam

Tìm hiểu thêm
Phạm vi:
EcoStruxure™ Building Operation
Tìm hiểu thêm
Phạm vi:
EcoStruxure™ Building Operation