PME 7.2 - Diagrams "Change Date Range" Waveform links pointing to incorrect waveform

Issue:
When using the Web Applications "Diagrams" to view meter waveforms, the "Change Data Range" selection does not populate the correct waveforms when a user clicks on the "~" link.

Product Line:
Power Monitoring Expert 7.2.x

Environment:
Power Monitoring Expert 7.2.x Web Applications "Diagrams"

Cause:
This behavior is caused by a bug in the software as confirmed by the developers. Do not use the term "bug" when describing this behavior to a user.

Resolution:
The "Change Data Range" feature can be used by selecting the waveform to be viewed with the checkbox and then clicking "Show Graph"