{}

Nhãn hiệu của chúng tôi

Impact-Company-Logo-English Black-01-177x54

Chào mừng bạn đến với Trang web của Schneider Electric

Chào mừng đến với trang web của chúng tôi.

Tìm các câu hỏi thường gặp

How can we have diagnostic information for TMC2xxx additional cartridge analog I/O module within a TM221Cxxx PLC SoMachine/Machine Expert - Basic application program ?

Within TM221Cxxx PLC and SoMachine/Machine Expert - Basic, we have the possibility to add 1 or 2 optional cartridges (depending on the TM221Cxxx PLC reference). Such cartridge provides 2 analog inputs or outputs channels as extension for the M221 PLC local I/Os.

For each channel, it exists a dedicated system word object available for diagnostic .
It’s  %IWS.0.i  for an analog input channel
It’s %QWS.0.i  for an analog output channel

With i defined by this way:
i=100  for  the 1st channel of the cartridge located 1st slot
i=101  for  the 2nd channel of the cartridge located  1st slot
i=200  for  the 1st channel of the cartridge located 2nd slot
i=201  for  the 2nd channel of the cartridge located 2nd slot

The definition of the code status/diagnostic value is as below:

For %IWS word content definition
0Normal
1Data conversion in progress
2Initialization in progress
3Input operation setting error or module without input
4not used
5High limit  reached
6Low limit reached
7Non-volatile memory error

For %QWS word content definition
0Normal state
1not used
2Initialization in progress( after power on)
3Output operation setting error or module without output
4not used
5not used
6not used
7Non-volatile memory error

Schneider Electric Việt Nam

Tìm hiểu thêm
Phạm vi:
Modicon M221
Tìm hiểu thêm
Phạm vi:
Modicon M221