In fact, the MES120 cards are designed to support DC voltages only. So, the Trip Circuit Supervision function on Sepam 80 will not work if the Trip Coil control voltage is an AC voltage.
The best solution would be to use another 3rd-party TCS relay to achieve this function. The ARTECHE range of relays may have a TCS relay which supports AC voltages.
If the customer wishes to monitor the status of the 3rd-party TCS function through the Sepam, then a DC contact from the 3rd-party relay could be wired to a Logic Input on the Sepam, and an assignment made in the SFT2841 Matrix to give an Alarm or Event in case of a TCS fault.
At a small number of sites, a "recitifier circuit" consisting of diodes, resistors, and capacitors was installed to effectively convert the AC voltage of the trip circuit to a DC voltage. The converted DC voltage was then wired to the Sepam logic inputs. However, we do not recommend this as the components may eventually fail, which would make the TCS function unreliable. It is best to use a TCS relay which supports AC control voltages.
AEDL3
Đã phát hành cho: Schneider Electric Việt Nam
In fact, the MES120 cards are designed to support DC voltages only. So, the Trip Circuit Supervision function on Sepam 80 will not work if the Trip Coil control voltage is an AC voltage.
The best solution would be to use another 3rd-party TCS relay to achieve this function. The ARTECHE range of relays may have a TCS relay which supports AC voltages.
If the customer wishes to monitor the status of the 3rd-party TCS function through the Sepam, then a DC contact from the 3rd-party relay could be wired to a Logic Input on the Sepam, and an assignment made in the SFT2841 Matrix to give an Alarm or Event in case of a TCS fault.
At a small number of sites, a "recitifier circuit" consisting of diodes, resistors, and capacitors was installed to effectively convert the AC voltage of the trip circuit to a DC voltage. The converted DC voltage was then wired to the Sepam logic inputs. However, we do not recommend this as the components may eventually fail, which would make the TCS function unreliable. It is best to use a TCS relay which supports AC control voltages.
AEDL3
Đã phát hành cho: Schneider Electric Việt Nam




Bạn cần trợ giúp?
Bắt đầu ở đây!
Tìm câu trả lời ngay. Tự tìm kiếm giải pháp, hoặc kết nối với một trong các chuyên gia của chúng tôi.
Liên hệ hỗ trợ
Liên hệ với nhóm chăm sóc khách hàng của Schneider để nhận thêm thông tin, được hỗ trợ kỹ thuật, trợ giúp khiếu nại và các thông tin khác.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Tìm kiếm câu hỏi thường gặp
Nhận câu trả lời bạn cần bằng cách duyệt tìm những Câu hỏi thường gặp (FAQ) liên quan đến chủ đề.
Liên hệ bộ phận bán hàng
Đăng ký bán hàng trực tuyến và chuyên gia của chúng tôi sẽ liên hệ với bạn.