{}

Nhãn hiệu của chúng tôi

Impact-Company-Logo-English Black-01-177x54

Chào mừng bạn đến với Trang web của Schneider Electric

Chào mừng đến với trang web của chúng tôi.

Tìm các câu hỏi thường gặp

What causes OFS to give a Polling rate overrun message?

Polling Rate Overrun is when OFS is requesting too much data and the PLC is not able to respond in a timely manner.  The Minimum Update Rate could be increased to give the PLC more time to respond.

-Locate the file named 'OFSinternal.xml' and make a backup copy of it. It should be in the following path: C:\ProgramData\Schneider Electric\OFS\3.60.0.0\
-Open the file named 'OFSinternal.xml' using 'Wordpad.
-Change the view to 'Word wrap to ruler'.
-Change the value of the "MinUpdateRate" value="1000".
-Save the changes.

NOTE:  The path above is for OFS v3.6 but it will also work for v3.5 but the path will be different.

Schneider Electric Việt Nam

Tìm hiểu thêm
Phạm vi:
Tìm hiểu thêm
Phạm vi: