{}

Nhãn hiệu của chúng tôi

Impact-Company-Logo-English Black-01-177x54

Chào mừng bạn đến với Trang web của Schneider Electric

Chào mừng đến với trang web của chúng tôi.

Tìm các câu hỏi thường gặp

What would cause Altivar 61 and Altivar 71 drive to not start with the terminal inputs on +24 and LI1?

Issue:
Altivar 61 and Altivar 71 drive does not start with the terminal inputs on +24 and LI1.

Product Line:
Altivar 61/71

Environment:
All

Cause:
Drive was in HMI mode with the F4 function key set to T/K.

Resolution:
- Check to see if the Functions keys are assigned to T/K  if so push that Function key to put the drive back in Remote mode.
- If its already in terminal mode check the supply voltage on LI1
- Check Programming in menu 1.6 the command menu to see if the drive is set for terminal control mode.
- Check that the switch SW1 is set for Source.

Schneider Electric Việt Nam

Tìm hiểu thêm
Phạm vi:
Tìm hiểu thêm
Phạm vi: