Is Metasys N2 communication protocol available for the Atlivar Process drives?

Article available in these languages: Tiếng Tây Ban Nha

Issue:
Customer is replacing an old ATV61 drive with Metasys N2 card.  Wants to be able to control and communicate to the drive using Metasys N2.

Product line:
Altivar Process, ATV630, ATV930,

Environment:
All

Cause:
Is there a cross refernce that includes Metasys N2

Resolution:
The Process Drives do not have a Metasys N2 Communication card available. Customer will need to use a third-party Modbus RTU to Metasys N2 gateway.
The Altivar 212 for Fan and Pump applications may be an option, as that drive does have integrated protocols including Metasys N2.