Tìm các câu hỏi thường gặp
How do I turn off "input phase loss"on a ATV312 drive?
Issue:
Deactivate Input Phase Loss on ATV312
Product Line:
ATV312
Environment:
All serial numbers
Cause:
Single phase input
Resolution:
Goto Flt menu
Goto IPO
Set to "no"
This parameter is only accessible on 3-phase drives.
Deactivate Input Phase Loss on ATV312
Product Line:
ATV312
Environment:
All serial numbers
Cause:
Single phase input
Resolution:
Goto Flt menu
Goto IPO
Set to "no"
This parameter is only accessible on 3-phase drives.