{}

Nhãn hiệu của chúng tôi

Chào mừng bạn đến với Trang web của Schneider Electric

Chào mừng đến với trang web của chúng tôi.
Tìm các câu hỏi thường gặp
What can cause a CFF fault on the ATV630 and ATV930 Process drives?
Issue:
CFF fault causes on the ATV630 and ATV930 Process drives.

Product Line:
ATV630 and ATV930 Process drives

Environment:
All 

Cause:
Option card removed, power board changed and not rated.
Use SoMove service section to identify the cause of the CFF.

Resolution:
At power on the hardware configuration is approved, if option card,
bower board has changed this error occurs.
Probable cause:
Option card removed, power board changed and not rated.
Use SoMove service section to identify the cause of the CFF.

Remedies:
- check all option cards if they are connected correctly.
- check if the power board / control block fit's to the drive.
- If the option card was removed intended, a factory setting needs to be performed

Schneider Electric Việt Nam

Tìm hiểu thêm
Phạm vi:
Tìm hiểu thêm
Phạm vi:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.