Where do you wire in remote speed reference to an ATV660?
Issue:
Wiring remote speed reference for an ATV660.
Product Line:
ATV660
Environment:
ALL
Cause:
Wiring / Programming
Resolution:
Customer Contacts for external analog input control signal.
TB1-11 = COM / Neutral
TB1-12 = AI3 Signal wire (programmable for 0-10, factory set for 4-20ma)
Program under : Complete Settings > Inputs/Outputs > AI/AQ tab > AI3 Configuration
Wiring remote speed reference for an ATV660.