undefined undefined
{}

Nhãn hiệu của chúng tôi

Impact-Company-Logo-English Black-01-177x54

Chào mừng bạn đến với Trang web của Schneider Electric

Chào mừng đến với trang web của chúng tôi.

Tìm các câu hỏi thường gặp

EcoStuxure Control Expert PLC and TeSysT on ProfibusDP: Extended Diagnostic Overflow Explained

On ProfibusDP network during initialization, the PLC (master) always asks slaves for diagnostic data (get_diagnostic telegram).
The slave will respond with diagnostic data.
Diagnostic data can consist of:
- standard diagnostic or
- standard diagnostic + extended diagnostic
The length of standard diagnostic data is fixed, while extended diagnostic data is manufacturer-specific, and its content and length are defined by the manufacturer.
TeSysT serves not only standard diagnostic but also extended diagnostic (manufacturer-specific) telegrams. The maximum length of a diagnostic telegram from TeSysT is 36bytes. The description of the vzTeSysT diagnostic telegram is in the attachment.
In Control Expert or older Unity software, the Profibus modules allocate 32 bytes by default for diagnostic telegram, which is not enough for TeSysT. It must be increased to 36 bytes or more.

Schneider Electric Việt Nam

Phần đính kèm

Extracted pages from LTMR - Profibus_DOCA0131EN-00.pdfExtracted pages from LTMR - Profibus_DOCA0131EN-00.pdf [88.31 KB]
Tìm hiểu thêm
Phạm vi:
Tìm hiểu thêm
Phạm vi: