{}

Nhãn hiệu của chúng tôi

Impact-Company-Logo-English Black-01-177x54

Chào mừng bạn đến với Trang web của Schneider Electric

Chào mừng đến với trang web của chúng tôi.

Tìm các câu hỏi thường gặp

What does the fault Current Phase Imbalance (Warning code 7) indicate on an LTMR Tesys T product?

Issue:
Customer is receiving a Current Phase Imbalance fault (Warning code 7)

Product line:
LTMR Tesys-T series

Environment:
All Tesys T models.

Cause:
Phase to Phase current draw through the Tesys T is unbalanced.

Resolution:
Phase to phase current draw through the Tesys T is unbalanced. This could be due to one of several causes.   If the phase to phase voltage is not balanced, the phase to phase current will be unbalanced also.   This could also be due to incorrect or poor wiring connections or due to unbalanced current draw by the motor itself.

Please see the attached file for details from the Tesys T / LTMR User manual.

Schneider Electric Việt Nam

Phần đính kèm

Current Phase Imbalance details.pdfCurrent Phase Imbalance details.pdf [80.5 KB]
Tìm hiểu thêm
Phạm vi:
Tesys TLocal TeSys thermal overload relays
Tìm hiểu thêm
Phạm vi:
Tesys TLocal TeSys thermal overload relays