{}

Nhãn hiệu của chúng tôi

Impact-Company-Logo-English Black-01-177x54

Chào mừng bạn đến với Trang web của Schneider Electric

Chào mừng đến với trang web của chúng tôi.

Tìm các câu hỏi thường gặp

How to resize Hierarchy Manager editor window in PME

Environment:
Power Monitoring Expert Hierarchy Manager.

Product Line:

PME 8.x, PME 9
PME 2020

Description of the issue:
In some scenarios when you use long hierarchy architecture and you have a huge list then you may see that the hierarchy editor window or each column in the editor window is not able to fit all the information.

Cause:
By default, the hierarchy editor window is not resizable

Resolution:
For PME2020, PME2020 CU1 and PME2020 CU2, kindly contact your technical support center and request Hotfix_Bug105047

For PME9 and PME8.x

Open ..\Power Monitoring Expert\Applications\HierarchyManager\Scripts\HierarchyManager

To change the behavior of the editor window open "view.nodedetails.js" using notepad ​for editing.
Update the "resizable:" parameter to "true" and save.

To change the behavior of the column in the editor window open "view.editor.reference.js" using notepad ​for editing.
Update the "resizable:" parameter to "true" and save.

You may have to restart the browser and IIS for the change to take effect.

Schneider Electric Việt Nam

Tìm hiểu thêm
Phạm vi:
Tìm hiểu thêm
Phạm vi: