{}

Nhãn hiệu của chúng tôi

Chào mừng bạn đến với Trang web của Schneider Electric

Chào mừng đến với trang web của chúng tôi.
Tìm các câu hỏi thường gặp
What are IDLF faults on a ATV680 drive?

Issue:

IDLF faults on a ATV680 enclosed product

 

Product Line:

ATV680

 

Environment:

IDLF faults

 

Cause:

n/a

 

Resolution:

 

When the device is in IDLE mode and you send a run command, but the device does not start to charge the bus within the adjusted energy saving timeout [idLt] (Factory settings: 5s // 8s for ATVx80 and ATVxB0), then the device will trip with IDLF.

Probable cause: The mains voltage is missing and the device cannot charge the DC Bus.

Remedies :Check mains voltage and ensure its availability. Check the DC bus voltage

 

 

Schneider Electric Việt Nam

Tìm hiểu thêm
Phạm vi:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.