Search FAQs
What needs to be done when prompted PrtF Fault on ATV61 display after installing replacement MCB and/or Power Board?
Issue:
ATV61 Drive Shows PrtF Fault after replacing MCB and/or Power Board.
Product Line:
Altivar 61
Environment:
All
Cause:
Altivar 61 with PrtF Fault
Resolution:
Need to Hit Enter, select Power ID (For 18-Pulse CPD=IP00, E-Flex =IP00, MCC = IP00,M-Flex =IP00, Open or Custom Enclosed units = IP20, etc.) Set for IPxx and hold Ent key for 2 seconds.
ATV61 Drive Shows PrtF Fault after replacing MCB and/or Power Board.
Product Line:
Altivar 61
Environment:
All
Cause:
Altivar 61 with PrtF Fault
Resolution:
Need to Hit Enter, select Power ID (For 18-Pulse CPD=IP00, E-Flex =IP00, MCC = IP00,M-Flex =IP00, Open or Custom Enclosed units = IP20, etc.) Set for IPxx and hold Ent key for 2 seconds.
Released for:Schneider Electric Global
Explore more
Range:
Explore more
Range: