Search FAQs
Do the TM3 analog input modules supply power to the inputs?
Issue:
Reading analog inputs on a TM3 module
Product line:
All TM3 analog input modules for all Products that can use the TM3 modules
Environment:
Exostruxure Machine Expert, So Machine Expert Basic, ( formally SoMachine and SoMachine Basic).
Cause:
Not able to read any analog inputs on card.
Resolution:
No the TM3 analog input modules need to have a loop supply or a self powered field device to power the input.
Reading analog inputs on a TM3 module
Product line:
All TM3 analog input modules for all Products that can use the TM3 modules
Environment:
Exostruxure Machine Expert, So Machine Expert Basic, ( formally SoMachine and SoMachine Basic).
Cause:
Not able to read any analog inputs on card.
Resolution:
No the TM3 analog input modules need to have a loop supply or a self powered field device to power the input.
Released for:Schneider Electric Global
Explore more
Range:
Explore more
Range: