AccuSine PCS+ Dual operation mode
Issue
The AccuSine+ can be used as a harmonic filter and power factor correction/Load balancing simultaneously. The total output current will be limited by harmonic current and the reactive current.

Product Line
AccuSine PCS+

Resolution
The total output of the harmonic filter in dual mode is governed by the following formula:
Formula

When the total current output of the active filter required exceeds the unit rating, the AccuSine PCS+ has a harmonic priority setting to determine which mode has priority.

Use percentage of harmonic priority to set output current split
  • 100% means output capacity utilized for harmonic correction, then left over can be used for Power factor correction.
  • 0% assigns fundamental (PF correction) current as the primary mode, left over used for harmonic correction.
The table below describes the relationship between harmonic current the reactive current
Output Table

Schneider Electric Global

AccuSine PCS+ Dual operation mode
Issue
The AccuSine+ can be used as a harmonic filter and power factor correction/Load balancing simultaneously. The total output current will be limited by harmonic current and the reactive current. 

Product Line
AccuSine PCS+

Resolution 
The total output of the harmonic filter in dual mode is governed by the following formula:
Formula

When the total current output of the active filter required exceeds the unit rating, the AccuSine PCS+ has a harmonic priority setting to determine which mode has priority.

Use percentage of harmonic priority to set output current split
  • 100% means output capacity utilized for harmonic correction, then left over can be used for Power factor correction.
  • 0% assigns fundamental (PF correction) current as the primary mode, left over used for harmonic correction.
The table below describes the relationship between harmonic current the reactive current
Output Table

Schneider Electric Global

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.