{}

Impact-Company-Logo-English Black-01-177x54
Share Price 
Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric corporate Website

Search FAQs

Scada webclient web page is empty in the browser

Issue
Scada webclient web page is empty in the browser
Web Client Web page

Product Line
PowerLogic Scada 7.x
PowerScada Expert 8.x

Environment
Webclient

Cause
The citect webclient is not added to the list of Trusted Sites.

Resolution
To add the citect webclient to the list of trust sites
1. Open Internet Explorer.
2. Navigate to the citect webclient webpage. For example http://win-l5ta9nc39v3/citect/
3. Click Tools > Internet Options.
4. On the Internet Options window, select the Security tab.
5. On the Security Tab, click on the Trusted Sites in "Select a zone to view or change security settings."
6. Click on the Sites button.

Internet Options

7. In the "Add this website to the zone:", enter the citect webpage and click Add.
Trusted sites

8. Click Close.
9. Click Ok to close the Internet Options window.
10. Refresh the Internet Explorer window to show the changes.


<Video Here>

Schneider Electric Global

Attachment(s)

WebClientBlankWebpage.zipWebClientBlankWebpage.zip [2.97 MB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: