Search FAQs
Video: How to Shutdown your Silcon UPS
Issue:
How to Shutdown your Silcon UPS
Product line:
Silcon DP300E
Environment:
All Product models, all serial numbers
Cause:
Shutdown Support
Resolution:
First step is to put the UPS into bypass
Hit the # Key and then Press "C" to change the option to yes
Press the # key again to save change.
The UPS is now in static bypass.
H3 LED will light indicating it is safe to operate Q3
Turn the Q3 switch on
H2 LED will light indicating it is safe to operate Q2
Turn the Q2 switch Off
Open the front door of the UPS and Press the Red button (acoustic alarm will sound for 30 seconds)
Open all battery breakers (or fuses)
Turn off the Q1 switch
Your UPS is now off