How to turn on or off capacitors using VarPlus Logic controller?
Issue
Power Factor is not meeting its target but its not using all the capacitors.

Product Line
VarPlus Logic VL6
VarPlus Logic VL12

Cause
The capacitor is set to Foff or Flty.  This will cause the capacitor never to turn on.  To view the status of the capacitor from the display:
1.  Arrow left until main screen.
2.  Arrow up or down to setup
3.  Arrow right to select setup
4.  Arrow down to the capacitor in question
5.  Arrow right to select that capacitor
6.  Arrow down multiple time to output to view the status.  It could be Fon, Foff, Flty, or Auto.
Please see picture below to help.
cap status

Resolution
If the output under info is set to anything other then AUTO or Fon then the following steps is how to change it.
1.  Arrow to the left until the main screen.
2.  Arrow up or down to setup
3. Arrow to the right twice
4.  Arrow down to OUT
5.  Arrow to the right
6.  Now arrow down to the capacitor that needs to be changed
7.  Once the correct one is selected arrow to the right
8.  Arrow up or down to select Fon (Fix on which means always on) or AUTO ( only on when needed)
9.  Arrow to the left until back to main screen
Please see picture below to help
change cap status

Schneider Electric Global

How to turn on or off capacitors using VarPlus Logic controller?
Issue   
Power Factor is not meeting its target but its not using all the capacitors.

Product Line   
VarPlus Logic VL6
VarPlus Logic VL12

Cause   
The capacitor is set to Foff or Flty.  This will cause the capacitor never to turn on.  To view the status of the capacitor from the display:
1.  Arrow left until main screen.
2.  Arrow up or down to setup
3.  Arrow right to select setup
4.  Arrow down to the capacitor in question
5.  Arrow right to select that capacitor
6.  Arrow down multiple time to output to view the status.  It could be Fon, Foff, Flty, or Auto. 
Please see picture below to help.
cap status

Resolution   
If the output under info is set to anything other then AUTO or Fon then the following steps is how to change it.
1.  Arrow to the left until the main screen.
2.  Arrow up or down to setup
3. Arrow to the right twice
4.  Arrow down to OUT
5.  Arrow to the right
6.  Now arrow down to the capacitor that needs to be changed
7.  Once the correct one is selected arrow to the right
8.  Arrow up or down to select Fon (Fix on which means always on) or AUTO ( only on when needed)
9.  Arrow to the left until back to main screen
Please see picture below to help
change cap status

 

Schneider Electric Global

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.