{}

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric corporate Website

Search FAQs
How to calculate PowerTag Energy read from Modbus Registers in INT64 format.
The energy values are stored in the INT64 bit format.

Formula to calculate the Energy for 64bit INT: Energy = ((register 4) * (2^48)) + ((register 3) * (2^32)) + ((register 2) *  (2^16)) + (register 1)

Schneider Electric Global

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: