Search FAQs
Why is my Panel Server blinking orange after removing a Modbus Device with EPC ?
Product Line
EcoStruxure Panel Servers
Environment
EcoStruxure Power Commission + PAS600L
Issue
PAS600L is blinking orange after the deletion of a connected Modbus device with EcoStruxure Power Commission (EPC).
Cause of Issue
This is a known issue when you delete a Modbus device with EPC.
Resolution
Connect to the Web Pages of the PAS600L and delete the product(s) from the Maintenance -> Devices Communication menu.
Refer to the pictures below.
![image.png](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0151H000009txI6QAI&oid=00DA0000000abSmMAI)
EcoStruxure Panel Servers
Environment
EcoStruxure Power Commission + PAS600L
Issue
PAS600L is blinking orange after the deletion of a connected Modbus device with EcoStruxure Power Commission (EPC).
Cause of Issue
This is a known issue when you delete a Modbus device with EPC.
Resolution
Connect to the Web Pages of the PAS600L and delete the product(s) from the Maintenance -> Devices Communication menu.
Refer to the pictures below.
Released for:Schneider Electric Global
Explore more
Product:
Explore more
Product: