PowerChute Network Shutdown version 4.4.2, 4.4.3, & 5.x web page is not accessible after installing onto standalone ESXi host.

Article available in these languages: Spanish

Issue:
After installing the PowerChute Network Shutdown version 4.4.2, 4.4.3, &5.x ova onto a standalone ESXi host, the web page is not accessible.

Product Line:
PowerChute Network Shutdown

Environment:
PowerChute Network Shutdown version 4.4.2, 4.4.3, & 5.x installed on VMware standalone ESXi host.

Cause:
Change to security settings.

Solution:
  1. Log in to the PowerChute virtual machine as root Login to PowerChute VM
  2. Run the command systemctl enable PowerChute to enable PowerChute to start when the VM is powered on.
  3. Next, run the command systemctl start PowerChute to start the PowerChute service.
  4. Next run the command systemctl status PowerChute to verify PowerChute service has started. Enable and start the PowerChute service
  5. Next open a web browser and navigate to the PowerChute web page. Example https://10.0.0.246:6547
The web page will launch, and you will be asked to set the PowerChute client up.


Schneider Electric Global

PowerChute Network Shutdown version 4.4.2, 4.4.3, & 5.x web page is not accessible after installing onto standalone ESXi host.

Article available in these languages: Spanish

Issue: 
After installing the PowerChute Network Shutdown version 4.4.2, 4.4.3, &5.x ova onto a standalone ESXi host, the web page is not accessible.

Product Line:
PowerChute Network Shutdown 

Environment:
PowerChute Network Shutdown version 4.4.2, 4.4.3, & 5.x installed on VMware standalone ESXi host.

Cause:
Change to security settings.

Solution:
  1. Log in to the PowerChute virtual machine as root Login to PowerChute VM
  2. Run the command systemctl enable PowerChute to enable PowerChute to start when the VM is powered on.
  3. Next, run the command systemctl start PowerChute to start the PowerChute service. 
  4. Next run the command  systemctl status PowerChute to verify PowerChute service has started. Enable and start the PowerChute service
  5. Next open a web browser and navigate to the PowerChute web page. Example https://10.0.0.246:6547
The web page will launch, and you will be asked to set the PowerChute client up. 


 
 

Schneider Electric Global

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.