{}

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric corporate Website

Search FAQs
What causes a STF fault on a ATS22 soft start?

Issue:

What causes a STF fault on a ATS22 soft start?

Product Line:

ATS22

Environment:

STF faults

Cause:

n/a

Resolution:

This is starting time detected faults. Make sure the tLS parameter (Set menu) is longer than the ACC (Set menu) parameter.

Would also make sure the In parameter matches the motor FLA and may need to increase the ILT parameter, if possible.

Schneider Electric Global

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: