THREE PHASE UPS EFFICIENCY COMPARISON CALCULATOR
Inputs
UPS System Attributes
System A
System B
Family
Select UPS Family
X
Select UPS Family
X
Configuration
X
Select UPS configuration
X
Rated Power
X
X
Select UPS rating
X
Model
GVSUPS10K0B4FS
X
Double Conversion
X
ECO Mode
X
Mode
Max. Allowed Load
10 kW
10 kW
100%
X
100%
X
UPS Quantity
1
X
1
X
Redundancy
N
X
N
X
10 kW
10 kW
Load
%
%
%
%
UPS A Efficiency
%
%
%
%
25
50
75
100
90.7
92.0
92.0
91.6
Load
%
%
%
%
UPS B Efficiency
%
%
%
%
25
50
75
100
94.3
96.7
97.5
97.9
Electricity Cost & Carbon Emission Factor
United States
X
€ 0.12 /kWh
X
0.038 kg/kWh
X
Location
Electricity Cost
CO2 Emission Factor
Results
UPS System
Efficiency
X
0
1.6
3.2
4.9
6.5
8.1
0
2.5k
5.0k
7.5k
10k
Energy (MWh)
Load (W)
A (SE E3SUPS10KFB1 - Double Conversion)
B (SE GVSUPS10K0B4FS - ECO Mode)
Comparison at 5.00 kW Load
Efficiency
UPS Losses
Annual Electricity
Annual CO2
System A
System B
92.0 %
96.7 %
434 W
168 W
3.81 MWh
1.48 MWh
2,310 kg
895 kg
Summary of Results
At a load of 5.00 kW, System B (SE GVSUPS10K0B4FS - ECO Mode) is more efficient than System A (SE E3SUPS10KFB1 - Double Conversion), which results in 266 W of heat load reduction, € 235 or 2,330 kWh in annual electrical savings, and 1,415 kg of avoided CO2 emissions per year.