{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
Video: How to setup a fault reset function on an ATV212 drive?
Issue:
ATV212 set up a fault reset function.

Product Line:
Altivar 212

Resolution:
RES terminal on the ATV212 which is parameter F113 is already programmed as fault reset from the factory.
F113 under F--- set to 10 for fault reset.
When RES is has +24VDC present on terminal that will perform a fault reset.

Warning:
UNINTENDED EQUIPMENT OPERATION
This configuration enables to reset the drive.  Make sure that this action will not endanger personnel or equipment in anyway.

Reminder that not all detected faults can be cleared.  Please check your ATV212 programming manual for a list of the faults that can be cleared using the fault reset function.

Schneider Electric South Africa

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: