What should be the dielectric test voltage for a Compact NSX MCCB?

Article available in these languages: Spanish

The dielectric test is related to the Insulation voltage "Ui" of the MCCB. For NSX MCCBs, the Ui is 800Vac. Accordingly and as per Table 12 of IEC 60947-2, the dielectric test voltage shall be 2000Vac for 1 second.