{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

Is it possible to change the protocol setting (PRP/RSTP etc.) in Micom Px4x relays from Easergy studio?

Issue:
Protocol setting (PRP/RSTP etc.) in Micom Px4x relays  through Easergy studio

Environment/Product line:
Micom P14x relay

Resolution :
Protocol setting has to be selected in relay's front display and it not  possible via Easergy Studio software.
So you have to select through relay’s front display then retrieve the information into EasergyStudio.
After that you can extract setting and able to see the require setting of your device.

Schneider Electric South Africa

Explore more
Range:
Easergy MiCOM P14x
Explore more
Range:
Easergy MiCOM P14x
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.