{}

Onze merken

Impact-Company-Logo-English Black-01-177x54

Welkom op de website van Schneider Electric

Welkom op onze website.

Populaire vragen (FAQ's) zoeken

Unable to configure GOOSE inputs for Vamp protection relays

Issue: Unable to configure GOOSE inputs for Vamp protection relays

Resolution: To be able to configure the GOOSE inputs for a VAMP relay you must select the Edition 2 Extensions check box when building the ICD file for the VAMP protection relay from VAMPset. This is what enables the GOOSE input configuration for the ICD file within VAMP SCD Editor.

Schneider Electric Belgium

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie